Description
Spirax Sarco Airodyn is a thermodynamic compressed air trap with an ENP anti-oxidation-treated exterior. Airody S can be supplied with a high-precision disc for high-purity applications.
Available Models
| Model | SKU |
|---|---|
| 1/2” Airodyn - screwed BSP | 6100600 |
Standards and Certificates
This product fully complies with the European Pressure Equipment Directive 97/23/EC. A certificate to EN 10204 3.1 is available (note: please specify the certificate requirement when ordering).
Port Size and Pipe Connections
½” threaded BSP or NPT; ¾” threaded NPT.
Pressure/Temperature Limits
| Parameter | Details |
|---|---|
| Maximum body design pressure | PN63 |
| PMA - Maximum allowable pressure | 63 bar g@120°C |
| TMA - Maximum allowable temperature | 400°C@42 bar g |
| PMO - Maximum operating pressure | 63 bar g@120°C |
| Minimum operating temperature | 0°C |
| TMO - Maximum operating temperature | 400°C@42 bar g |
| Can shut off | PMOB - Back pressure must not exceed 80% of inlet pressure under any circumstances; otherwise, the trap cannot shut off. |
| Minimum operating differential pressure | 0.25 bar |
| Maximum cold hydraulic test pressure | 95 bar g |
Capacity and KV Values
| Port Size | KV Value | Conversion Formula |
|---|---|---|
| ½” | 3.09 | CV (UK) = KV×0.963 CV (US) = KV×1.156 |
| ¾” | 3.09 | CV (UK) = KV×0.963 CV (US) = KV×1.156 |
Materials
| No. | Component | Material |
|---|---|---|
| 1 | Body | Stainless steel ASTM A743 Gr. CA40F |
| 2 | Cap | Stainless steel AISI 416 |
| 3 | Disc | Stainless steel BS 1449 420 S45 |
| 4 | Strainer screen | Stainless steel BS 1449 304 S16 |
| 5 | Strainer cap | Stainless steel AISI 416 |
| 6 | Strainer cap gasket | Stainless steel BS 1449 304 S16 |
Weight
| Port Size | Weight (kg) |
|---|---|
| ½” | 0.77 |
| ¾” | 0.95 |
Disposal
This product is recyclable and will not cause ecological problems when disposed of properly.
Ordering Information
Example: 1 - ½” Spirax Sarco Airodyn compressed air trap, screwed BSP connection.
Safety Information, Installation and Maintenance
Refer to the installation and maintenance guide supplied with the product (IM - S48 - 06).
Installation Instructions
The trap should preferably be installed in a horizontal pipe, but it can also be installed in a vertically downward pipe.