Description
Spirax Sarco EL2270 and EL2271 temperature sensors. EL2270 is a PT100 platinum resistance temperature sensor for general industrial applications. It is a three-wire RTD compliant with EN60751: Class A and can be connected to temperature indicators or controllers with three-wire PT100 inputs. For specific applications, options include a fast-response version with a 40mm insertion depth and a compact sensor with a 39mm insertion length and ¼” BSP threaded connection. EL2271 combines a PT100 sensor and transmitter. The three-wire sensing element complies with EN60751: Class A, while the transmitter provides a 4 - 20mA output and complies with ATEX 1G EExia IIC/IIB T4/T5/T6. It can be calibrated on site from -50°C to 500°C. The 4 - 20mA output can be connected to equipment with a corresponding input. Three-point calibration transmitter versions are also available.
Available Models
| Model | SKU |
|---|---|
| EL2270 PT100 25MM | 3221260 |
| EL2270 PT100 50MM | 3221261 |
| EL2270 PT100 75MM | 3221262 |
| EL2270 PT100 125MM | 3221263 |
| EL2270 75MM KIT | 322K1262 |
| EL2270 125MM KIT | 322K1263 |
| EL2271 100 - 250 °C 50MM | 3221365 |
| EL2271 100 - 250 °C 75MM | 3221368 |
| EL2271 100 - 250 °C 125MM | 3221391 |
| EL2271 75MM KIT 100 - 250 °C | 322K1368 |
| EL2271 125MM KIT 100 - 250 °C | 322K1391 |
| EL2270\1 pocket 50 MM | 3221294 |
| EL2270\1 pocket 75 MM | 3221295 |
| EL2270\1 pocket 125MM | 3221292 |
Thermowells
Three types of thermowells are available:
-
Thin-wall thermowell with a ½” NPT threaded connection;
-
Tapered-bore thermowell with a ½” NPT threaded connection;
-
Sanitary thermowell compliant with 3A sanitary standards, with a 1½” sanitary clamp connection (ASME BPE), electropolished to 0.4μm; certification is available on request. The compact EL2270 is supplied without a thermowell. Thermowells are made of 316 stainless steel and are rated for a maximum temperature of 500°C. Select the thermowell according to sensor insertion length ‘D’. Thermowell dimension “F” is shorter than sensor dimension “D”. Thermowells for 225mm and 725mm sensors are for non-flowing applications only.
Technical Specifications
| Product | EL2270 (fast-response version available on request) | EL2271 |
|---|---|---|
| Enclosure | KNE - aluminium alloy - epoxy coated | KNE - aluminium alloy - epoxy coated |
| Sensor probe | 316 stainless steel | 316 stainless steel |
| Connection | ½” NPT | ½” NPT |
| Cable entry | M20 with cable gland compliant with BS 4568, Chapter 1 | M20 with cable gland compliant with BS 4568, Chapter 1 |
| Ingress protection | IP65 | IP65 |
| Ambient temperature (minimum) | -50 °C | -50 °C |
| Ambient temperature (maximum) | +70 °C | +85 °C |
Electronic Specifications
| Product | EL2270 | EL2271 |
|---|---|---|
| Temperature range | -50 °C - +500 °C | -50 °C - +500 °C |
| Output | Pt100 compliant with EN 60751: Class A | Loop-powered 4 - 20 mA |
| Sensor fault output | - | Normally 23 mA |
| Power supply | - | 10 - 30 Vdc |
| Maximum loop resistance | - | 636 at 24 Vdc, 909 at 30 Vdc |
| Maximum loop current (+、 - wiring) | - | Uo = 30 Vdc, Io = 120 mA, Pi = 800 mW, Ci = 6.2 μF, Li = 110 μH |
| Maximum sensor circuit values (wiring 13) | - | Uo = 6.4 Vdc, Io = 42.6 mA, Po = 37.1 mW; Group II B: Co = 500 μF, Lo = 50 mH; Group II C: Co = 20 μF, Lo = 10 mH |
| EMC emissions | - | EMC Directive 89 / 336 / EEC, EN 61326:1997 / A1, 1998 / A2.2001 |
Pressure/Temperature Limits
Temperature sensors can be used in applications where process temperature remains within the specified range. Thermowells must be added for high-temperature and high-pressure applications. For air and steam applications, fluid velocity should be below 45m/s. For liquid applications, a velocity of 5m/s is recommended; 700mm and 200mm versions are for non-flowing applications only. Products have different pressure and temperature limits with and without a thermowell, and certain operating regions are not permitted.