Description

Spirax Sarco FT43 cast iron float-operated steam trap for DN80 and DN100 applications, with an integrated automatic air vent. Horizontal installation only; flanged connection. A 3/8” BSP or NPT threaded hole can be drilled in the valve cover as required for installation of a blowdown valve.

Standards and Certificates

This product complies with the European Pressure Equipment Directive 97/23/EC and can be supplied with a CE mark when required. An EN 10204 2.2 certificate is available. Please specify the certificate requirement when ordering.

Limiting Conditions

Valve design conditionPN16
PMA maximum allowable pressure16 bar g
TMA maximum allowable temperature220°C
PMO maximum operating pressure13 bar g
TMO maximum operating temperature220°C
Maximum designed cold hydraulic test pressure24 bar g

Sizes and Pipe Connections

DN80 and DN100 use EN1092 PN16 standard flanges. JIS/KS 10 flange connections are available as required.

Materials

No.ComponentMaterial
1BodyCast iron (DIN 1691 GG 20)
2Cover bolts and nutsSteel (BS 4439 Gr. 8.8, BS 3692 Gr. 8)
3Cover gasketReinforced exfoliated graphite
4CoverCast iron (EN JL 1040)
5Main valve assemblyStainless steel (BS 3146 Part. 2 ANC 2)
6Main valve assembly gasketReinforced exfoliated graphite
7Main valve assembly bolts and nutsStainless steel (BS 6105 A4 - 80)
8Float lever mechanismStainless steel (BS 1449 304 S16)
9Air vent assemblyStainless steel
10Air vent seat gasketStainless steel (BS 1449 409 S19)

Maximum Differential Pressure

SizeFT43 - 4.5FT43 - 10FT43 - 14
DN80 and DN1004.5 bar10 bar13 bar

Capacity

The capacities shown are condensate capacities at saturation temperature. When subcooled water is discharged, the air vent assembly increases condensate capacity. During start-up, the thermostatic air vent assembly opens, increasing condensate capacity.

ΔP (bar)0.51234.571013
Minimum additional cold-water capacity for DN80 and DN100 (kg/h)10801200124013401400200026003200

Weight

SizeWeight (kg)
DN8072
DN10074

Safety Information, Installation and Maintenance

For detailed information, refer to the installation and maintenance instructions supplied with the product (IM-S02-30). Install according to the flow direction indicated on the body. Ensure that the float arm is horizontal so the float can move freely in the vertical direction.

Disposal

This product is recyclable and, when disposed of properly, presents no environmental hazard.

Ordering Information

Example: 1 - Spirax Sarco DN100, FT43 - 4.5 float-operated steam trap, EN1092 PN16 flanged connection, cast iron body, with air vent assembly.

WeChat ID copied