Description

Spirax Sarco FT14 float and thermostatic steam trap with a flanged connection, ductile iron body, and built-in automatic air vent. The flanged design allows in-line servicing without removing the trap from the pipeline.

Available Models

  • FT14(R-L): Horizontal connection with flow from right to left

  • FT14(L-R): Horizontal connection with flow from left to right

  • FT14(V): Vertical connection with downward flow

Other Options

  • FT14C: In addition to an air vent, includes a steam lock release device (SLR) to prevent steam locking in the system. The letter “C” is included in the model designation.

  • FT14X: Includes a built-in strainer.

Capsule

The BP99/32 capsule can be used with superheated steam, with superheat of 150°C@0 bar g and 50°C@32 bar g.

Standards and Certification

Complies with the European Pressure Equipment Directive 97/23/EC. An EN 10204 2.2 certificate is available when specified at the time of ordering.

Materials

No.ComponentMaterial
1BodyDuctile iron DIN 1693 GGG 40
2Cover boltsBS 3692 Gr.8.8
3Cover gasketReinforced exfoliated graphite
4CoverDuctile iron DIN 1693 GGG 40
5Main valve seatStainless steel BS 970 431 S29
6Main valve/air vent seat gasketStainless steel BS 1449 409 S19
7Main valve assembly screwsStainless steel BS 6105 CI A2-70
8Float and lever mechanismStainless steel BS 1449 304 S16
9Air vent assemblyStainless steel
10Pivot bracketStainless steel BS 1449 304 S16
11Pivot pinStainless steel
12SLR assemblyStainless steel BS 970 303 S21
13SLR gasketStainless steel BS 1449 304 S16
14SLR sealGraphite
15Erosion-resistant guide (DN25 only)Stainless steel BS 970 431 S29
16Main valve spring (DN25 only)Stainless steel BS 2056 302 S26

Sizes and Pipeline Connections

Available sizes are DN15, DN20, and DN25. Flange standards include EN 1092 PN16, ANSI 150, and JIS/KS 20.

Weight

SizeWeight (kg)
DN154.5
DN205.0
DN256.5

Operating Range

ItemDetails
Body design conditionsPN16
PMA maximum allowable pressure16 bar g@100°C
TMA maximum allowable temperature250°C@13 bar g
Minimum allowable temperature-10°C
PMO maximum operating pressure14 bar g
TMO maximum operating temperature250°C@13 bar g
Minimum operating temperature0°C
$\triangle PMX$ maximum differential pressure (FT14-4.5)4.5 bar
$\triangle PMX$ maximum differential pressure (FT14-10)10 bar
$\triangle PMX$ maximum differential pressure (FT14-14)14 bar
Design maximum cold hydraulic test pressure24 bar g

Safety Information, Installation, and Maintenance

For detailed information, refer to the installation and maintenance instructions supplied with the product (IM-S02-13). During installation, ensure that the fluid flow direction matches the arrow on the body and that the float arm is horizontal, allowing the float to move freely in the vertical direction. The flow direction can be changed on site when required.

Disposal

This product is recyclable and, when disposed of properly, will not cause environmental harm.

Ordering Information

Example: 1 - Spirax Sarco DN25 FT14-4.5(R-L) float and thermostatic steam trap, DN16 flanged connection, with air vent, with connection direction changeable on site.