Description
Spirax Sarco FT14 float and thermostatic steam trap with a flanged connection, ductile iron body, and built-in automatic air vent. The flanged design allows in-line servicing without removing the trap from the pipeline.
Available Models
-
FT14(R-L): Horizontal connection with flow from right to left
-
FT14(L-R): Horizontal connection with flow from left to right
-
FT14(V): Vertical connection with downward flow
Other Options
-
FT14C: In addition to an air vent, includes a steam lock release device (SLR) to prevent steam locking in the system. The letter “C” is included in the model designation.
-
FT14X: Includes a built-in strainer.
Capsule
The BP99/32 capsule can be used with superheated steam, with superheat of 150°C@0 bar g and 50°C@32 bar g.
Standards and Certification
Complies with the European Pressure Equipment Directive 97/23/EC. An EN 10204 2.2 certificate is available when specified at the time of ordering.
Materials
| No. | Component | Material |
|---|---|---|
| 1 | Body | Ductile iron DIN 1693 GGG 40 |
| 2 | Cover bolts | BS 3692 Gr.8.8 |
| 3 | Cover gasket | Reinforced exfoliated graphite |
| 4 | Cover | Ductile iron DIN 1693 GGG 40 |
| 5 | Main valve seat | Stainless steel BS 970 431 S29 |
| 6 | Main valve/air vent seat gasket | Stainless steel BS 1449 409 S19 |
| 7 | Main valve assembly screws | Stainless steel BS 6105 CI A2-70 |
| 8 | Float and lever mechanism | Stainless steel BS 1449 304 S16 |
| 9 | Air vent assembly | Stainless steel |
| 10 | Pivot bracket | Stainless steel BS 1449 304 S16 |
| 11 | Pivot pin | Stainless steel |
| 12 | SLR assembly | Stainless steel BS 970 303 S21 |
| 13 | SLR gasket | Stainless steel BS 1449 304 S16 |
| 14 | SLR seal | Graphite |
| 15 | Erosion-resistant guide (DN25 only) | Stainless steel BS 970 431 S29 |
| 16 | Main valve spring (DN25 only) | Stainless steel BS 2056 302 S26 |
Sizes and Pipeline Connections
Available sizes are DN15, DN20, and DN25. Flange standards include EN 1092 PN16, ANSI 150, and JIS/KS 20.
Weight
| Size | Weight (kg) |
|---|---|
| DN15 | 4.5 |
| DN20 | 5.0 |
| DN25 | 6.5 |
Operating Range
| Item | Details |
|---|---|
| Body design conditions | PN16 |
| PMA maximum allowable pressure | 16 bar g@100°C |
| TMA maximum allowable temperature | 250°C@13 bar g |
| Minimum allowable temperature | -10°C |
| PMO maximum operating pressure | 14 bar g |
| TMO maximum operating temperature | 250°C@13 bar g |
| Minimum operating temperature | 0°C |
| $\triangle PMX$ maximum differential pressure (FT14-4.5) | 4.5 bar |
| $\triangle PMX$ maximum differential pressure (FT14-10) | 10 bar |
| $\triangle PMX$ maximum differential pressure (FT14-14) | 14 bar |
| Design maximum cold hydraulic test pressure | 24 bar g |
Safety Information, Installation, and Maintenance
For detailed information, refer to the installation and maintenance instructions supplied with the product (IM-S02-13). During installation, ensure that the fluid flow direction matches the arrow on the body and that the float arm is horizontal, allowing the float to move freely in the vertical direction. The flow direction can be changed on site when required.
Disposal
This product is recyclable and, when disposed of properly, will not cause environmental harm.
Ordering Information
Example: 1 - Spirax Sarco DN25 FT14-4.5(R-L) float and thermostatic steam trap, DN16 flanged connection, with air vent, with connection direction changeable on site.