Description

Spirax Sarco LP11-4 level sensor is used with Spirax Sarco LCS1350 level controller for on/off level control and alarm applications in steam boilers, tanks, and other vessels.

The 4-probe version is especially suitable for installations with a 3-lamp electronic level/alarm display. The sensor body is grounded through the threaded connection, while the boiler or tank normally provides the ground return path. The sensor can also be used in concrete or plastic tanks by using one probe as the ground connection or by providing a separate grounding rod or plate.

The 4 probes of LP11-4 are removable and can be cut to the required length before installation. Probes must be ordered separately. When a probe is immersed in conductive liquid, an electrical circuit is completed. When the liquid level falls below the probe, resistance increases and a signal is sent to the controller, indicating that the probe is out of the liquid. Note: the sensor must not be installed outdoors without additional protection.

Available Probe Lengths

Probe length is 1000mm. The maximum length when two probes are connected is 2095mm.

Pressure/Temperature Limits

PN40
Maximum pressure32 bar g(464 psi g)
Maximum temperature239°C(462°F)
Maximum ambient temperature70°C(158°F)
Minimum ambient temperature-20°C(-4°F)

Technical Data

Enclosure ratingIP54 (refer to the controller installation and maintenance guide)
Maximum cable length (sensor to controller)2095 mm (82.5”)
Minimum sensing depth75 mm (3”)
Minimum conductivity when used with LCS13500.5μS/cm @ 25℃

Materials

ComponentMaterial
BodyAustenitic stainless steel BS EN 10088-3 (1.4306)
ProbeAustenitic stainless steel Type 316/ 316L
Probe insulation sleevePFA (Per Fluor Alkoxy)
Lower wiring coverPPS (Polyphenyline sulphide)
Upper wiring coverPPS (Polyphenyline sulphide)
Gland support washerElastomeric thermoplastic
Cable glandPolyamide
Probe retainerPEEK (Polyaryletherketone) Grade 450G

Safety Information, Installation, and Maintenance

  • Warning: If this product is exposed to excessive heat, the plastic materials contained in the product will release toxic fumes.

  • Installation: LP11-4 is designed for installation in a flange or cover with a BSP Rp1 (1” BSP tapered) threaded hole. The thread specification must be stated when ordering. When installed in a boiler or a tank subject to severe turbulence, a protection tube with a minimum nominal bore of 80mm is recommended. Outdoor installations must be protected from wind and rain.

  • Wiring: Wiring for LP11-4 is simple and direct. Wiring connectors are available as spare parts, and the terminals are color-coded for identification. If the wiring needs to be disconnected, simply open the wiring assembly; it is not necessary to remove the cable gland.

  • Maintenance: Although boiler water level controls require regular testing, this product requires no special maintenance.

Product Description

Austenitic stainless steel body and sensor probes with PFA probe insulation, for boilers with a maximum pressure of 32 bar g (239℃).

Ordering Information

Example: 1 - Spirax Sarco LP11-4 sensor (BSP), probe length 1000mm.

Available Spares

  • LP11-4 wiring connector: includes 6 straight connectors and 2 circular connectors

  • LP11-4 probe installation kit: includes 1 probe connector, 1 locking screw nut, and 2 probe retainers

Weight (Approximate)

Weight (kg)
1.15
WeChat ID copied