Description

Spirax Sarco TD32F flanged thermodynamic steam traps are maintainable, medium-pressure thermodynamic steam traps with an integral strainer and flanged connections, suitable for medium-pressure applications. TD32FLC is specifically designed for draining condensate under low-load conditions, such as in steam mains. TD32FA and TD32FALC feature an integral anti-air-binding disc for air discharge during start-up.

Standards

This product complies with the European Pressure Equipment Directive 97/23/EC.

Certificates

An EN10204 3.1 certificate is available for this product (note: specify the certificate when ordering).

Sizes and Pipe Connections

DN15, 15LC, 20, 20LC, 25 and 25LC; ANSI B 16.5 Class 150 and 300, DIN 2501 PN40, and JIS/KS 10, 16, 20 flanges.

Other Options

Insulation cover (DN15 and DN20 only): prevents excessive heat loss and excessively frequent cycling when the steam trap operates in low-temperature, windy and rainy conditions.

Limiting Conditions (ISO 6552)

Body design conditionsPN40
PMA - Maximum allowable pressure40 bar g
TMA - Maximum allowable temperature400 ℃
Minimum allowable temperature0 ℃
PMO - Maximum operating pressure32 bar g
TMO - Maximum operating temperatureTD32F and TD32FLC: 400 ℃; TD32A and TD32FALC: 255 ℃
Minimum operating temperature0 ℃
Minimum operating pressure0.25 bar g
PMOB maximum operating back pressure is 80% of upstream pressure-
Design maximum cold hydraulic test pressure60 bar g

Operating Range

There are areas in which the product cannot be used, and the applicable range varies by model.

Materials

ItemPartMaterial
1BodyStainless steel ASTM A743 CA - 40
2BonnetStainless steel AISI 416
3DiscStainless steel BS 1449 420 S45
4Strainer screenStainless steel ASTM A240 316L (the strainer screens for TD32FA and TDFALC are 100 mesh; other models have a 0.8mm strainer screen)
5Strainer coverStainless steel AISI 416
6Strainer cover gasketStainless steel BS 1449 304 S16
7Insulation cover (optional, DN15 and 20 only)Aluminum
8FlangeSteel DIN 17243 C22.8 Ws 1.0460

Weight

SizeWeight (kg)
DN15 and 15LC2.4
DN20 and 20LC3.1
DN25 and 25LC4.2

Capacity

Condensate capacity varies with differential pressure. Refer to the relevant charts for details (the capacity charts in the document do not provide a detailed numerical relationship; this section is for general reference only).

Safety Information, Installation and Maintenance

For detailed information, refer to the installation and maintenance guide supplied with the product (IM - P068 - 26). TD32F is designed for horizontal installation with the bonnet facing upward. If there is downstream back pressure, installing a check valve is recommended. If discharging directly to atmosphere, installing a silencer downstream is recommended. For easier maintenance, isolation valves should be installed upstream and downstream of the steam trap.

Disposal

This product is recyclable and, when disposed of properly, will not cause environmental pollution.

Ordering Information

Example: 1 - Spirax Sarco DN15 TD32FALC low-capacity steam trap, PN40 flanged connection, with integral strainer and anti-air-binding disc.