Description

Spirax Sarco AVC32 is a repairable pressure-balanced thermostatic air vent made of carbon steel, with a built-in flat filter and in-line connections for steam systems. All pressure-containing components are supplied by TÜV-certified suppliers, and the manufacturing process complies with AD-Merkblatt WO/TRD100 standards.

Standard: This product complies with the European Pressure Equipment Directive 97/23/EC. Certificate: An EN 10204 3.1.B material certificate is available for this product. Note: Please specify the certificate requirement when placing the order.

Sizes and Pipe Connections

½”, ¾” and 1” threaded connections, BSP or NPT.

½”, ¾” and 1” socket-weld connections to BS 3799.

½”, ¾” and 1” butt-weld connections to EN 12 627.

DN15, 20 and 25 flanged connections to EN 1092 PN40.

ANSI B 16.5 Class 150 and 300, JIS/KS 10K and JIS/KS 20K.

Operating Range and Limitations (ISO6552)

Valve design conditionPN40
PMA - Maximum allowable pressure50bar g@50 ℃
TMA - Maximum allowable temperature400°C@35 bar g
Minimum allowable temperature-60 ℃
PMO - Maximum saturated steam pressure32 bar g
TMO - Maximum operating temperature287°C@32 bar g
Minimum operating temperature0 ℃
Maximum design cold hydraulic test pressure75 bar g

Kv Values

SizeDN15 - ½”DN20 - ¾”DN25 - 1”
Kv0.80.80.8

Conversion formulas: Cv(UK) = Kv×0.963 Cv (US) = Kv×1.156

Materials

No.ComponentMaterial
1BonnetDIN 17243 C22.8 (W/S 1.0460)/carbon steel ASTM A105N
2CapsuleStainless steel
3SeatStainless steel BS 970 431 S29
5Filter screenStainless steel AISI 304
7Bonnet gasketStainless steel-reinforced sheet graphite
8BodyCarbon steel DIN 17243 C22.8 (W/S 1.0460)/ASTM A105N
9Bonnet boltsStainless steel (M10 x 30) A2-70
17SpringStainless steel
18BaffleStainless steel

Weight

SizeThreaded/Welded WeightFlanged Weight
½”DN151.4kg2.9kg
¾”DN201.4kg3.5kg
1”DN251.5kg4.1kg

Installation Notes

Install AVC32 with the capsule in a horizontal position and the bonnet at the top.

AVC32 should be installed where air is likely to accumulate, such as at the highest point of a steam main or piece of equipment. The discharge outlet should be directed to a safe location.

For ease of maintenance, isolation valves are recommended upstream and downstream of the air vent. The air vent should not be insulated.

Disposal Information

This product is recyclable and will not create an ecological problem when properly disposed of.

Ordering Information

Example: 1 - Spirax Sarco ½” AVC 32 air vent, BSP threaded connection.

WeChat ID copied