Spirax Sarco EP6 electrical positioner can be used with linear or rotary actuators featuring NAMUR connections to provide accurate correspondence between control valve travel and the positioner’s input signal (mA). The EP6 positioner has a die-cast aluminum housing suitable for outdoor installation. When installed on a linear actuator, the corresponding travel range is 20mm to 150mm. When installed on a rotary actuator, the corresponding travel range is 55-90°. Multiple positioner mounting kit options are available, and the model must be specified when ordering. EP6 positioner includes a pressure gauge as standard for displaying the compressed air pressure supplied to the actuator. This actuator accepts an mA control signal and has a maximum compressed air pressure of 7barg. EP6 positioner can be used for either direct or reverse action. EP6 positioner must be supplied with high-quality air meeting ISO 8573-1:2010 Class 3:3:2. EP6 positioner can be used with Spirax Sarco BVA300, PN9000 series, TN2000 series, and DC series actuators, as well as other actuators with NAMUR connections.
Materials
| Component | Material | Finish |
|---|
| Housing and cover | Die-cast aluminum | Corrosion-resistant coating |
| Mounting bracket | Carbon steel | RAL9016 |
Technical Specifications
| Input signal | 4-20 mA (minimum increment 8 mA for split-range control) |
|---|
| Input impedance | Maximum 250 ± 15 Ω |
| Compressed air | 1.4 - 7.0 bar |
| Air quality | Dry, oil-free, and free of contaminants; complies with ISO 8573-1:2010 Class 3:3:3 |
| Output pressure | 0 - 100% supply pressure |
| Travel range | 20mm – 150mm; 55 ° - 90 ° |
| Action | Single-acting / double-acting |
| Operating temperature | -20 ℃ - +70 ℃ |
| Air flow rate | 80 LPM @ 1.4 bar |
| Steady-state air consumption | 2.4 LPM @ 1.4 bar |
| Air connection | ¼” NPT thread |
| Sensitivity | Single-acting: ± 0.2% of full travel; double-acting: ± 0.5% of full travel |
| Hysteresis | ± 1% of full travel; single-acting: ± 1% of full travel |
| Linearity | Double-acting: ± 2% of full travel |
| Repeatability | ± 0.5% of full travel |
| Electrical connection | M20 cable entry, terminal block for 0.5 - 2.5mm² wires |
| Enclosure rating | IP66 linear |
| Weight | 2.8 kg (linear positioner body); 1.2 kg (EY1/EY2/EY3/EY4 mounting kit); 0.9 kg (UY1/UY3 mounting kit); 4.1 kg (rotary positioner and mounting kit) |
Positioner Selection Guide
| Mounting type | Explosion protection | Non-explosion-proof; linear: select the mounting kit according to page 4; rotary: supplied with standard mounting kit |
|---|
| Electrical connection type | M20 - ¼ ” NPT standard type | |
Mounting Kits
| Mounting position | Actuator model | Valve model | Valve size | Mounting bracket model |
|---|
| Center | PN9100 | Two-way and three-way Spira-Trol TM valves | DN15 - DN50 | EY1 / EY3 |
| PN9200 | | DN15 - DN100 | |
| PN9300 | | | |
| TN2030 | Two-way and three-way Spira-Trol TM valves | DN15 - DN100 | EY1 / EY3 |
| TN2150 | | | |
| TN2300 | | DN125 - DN300 | EY2 / EY4 |
| TN2400 | | | |
| TN2270 | | | |
| Left side | PN9100 | Two-way and three-way Spira-Trol TM valves | DN15 - DN50 | UY3 |
| PN9200 | | DN15 - DN100 | |
| PN9300 | | | |
| TN2030 | Two-way and three-way Spira-Trol TM valves | DN15 - DN100 | Not applicable |
| TN2150 | | | |
| TN2300 | | DN125 - DN300 | UY1 |
| TN2400 | | | |
| TN2270 | | | |
Safety Information, Installation, and Maintenance
For more information, see the EP6 Installation and Maintenance Guide.
Available Models
| Model | SKU |
|---|
| EP6 Positioner For Side mounting(DN15 - 100)+ FR20A | 3440252+3440214+5400 |
| EP6 Positioner For Center mounting(DN15 - 100)+ FR20A | 3440252+3440206+5400 |
| EP6 Exd IIBT5(DN15 - 100) For Side Mounting+ FR20A | 3440254+3440214+5400 |
| EP6 Exd IIBT5(DN15 - 100) For Center Mounting+ FR20A | 3440254+3440206+5400 |