Description

Spirax Sarco LC2650 level controller is designed for conductive fluids and provides on/off or modulating level control for boilers, tanks, and vessels. Operating limits are 32bar@239°C. Two alarm channels can be independently configured for high- or low-level alarms. The minimum conductivity is 5us/cm or 5ppm when used with LP20 and PA20.

The front panel features an LCD and five buttons. In operating mode, the LCD displays operating information and can show level fluctuation trends over a configured period. Common data is displayed across several sequential screens during operation. The test menu provides diagnostic functions, including input measurement and output setup from the front panel. All commissioning parameters are password protected to prevent unwanted or incorrect settings.

The product can communicate with adjacent products through an infrared bus and can be assigned as a master or slave. Panel, DIN rail, or baseplate mounting is available.

Key Features

  • Modulating or on/off boiler water level control using capacitive sensors.

  • Adjustable integral action.

  • Single-element, two-element, or three-element control.

  • One graphical LCD and five buttons.

  • Graphical display of status, PV percentage, alarms, and trends.

  • Infrared communications.

  • EIA 485/Modbus communications.

  • UL and TUV approved.

Approvals

  • LC2650 complies with the EMC Directive 2017/30/EU and its requirements for heavy industrial environments, with a detailed EMC assessment. Reference: UK Supply BH LC2650 2008.

  • Complies with the Low Voltage Directive and the safety requirements of EN 61010-1:2001 for electrical equipment used for measurement, control, and laboratory applications.

  • Type tested as a level controller in accordance with Vd TÜV Water Control Equipment 100(07:2006) and UL listing (pending).

Applications

  • On/off operation: Pump on/off control, 2 alarm outputs, and an isolated 4 - 20mA level output. On/off solenoid valve control can also be provided instead of pump control.

  • Modulating control: Control valve operation by valve motor drive or 4 - 20mA control signal, 2 alarm outputs, and an isolated 4 - 20mA level output.

  • Two-element or three-element modulating control: Control valve operation by valve motor drive or 4 - 20mA control signal, 2 alarm outputs, isolated 4 - 20mA level output, steam flowmeter feedback signal, and feedwater flow forward signal.

Input Function

LC2650 compares the input signal with the user-defined set point and changes the output signal to control the water level in a boiler or tank.

Outputs

The product control signal can be connected to a pump or modulating valve. Relay outputs are also provided for high- and low-level alarms, together with isolated 0 - 20mA or 4 - 20mA retransmission. Parameters can be transmitted through RS485/MODBUS communications.

Additional Features

An additional filter provides increased damping under fluctuating conditions.

Technical Specifications

ItemDetails
Power supplySupply voltage: 110 - 240 VAC, 50/60HZ. Power consumption: 7.5W (maximum)
EnvironmentIndoor use only. Maximum altitude: 2000 m (6562 ft) above sea level. Ambient temperature range: 0 - 55 °C. Maximum relative humidity: 80% at 31 °C, linearly decreasing to 50% at 40 °C. Overvoltage category: III. Pollution degree: 2 (as supplied), 3 (when installed in an enclosure) - minimum IP54 or UL50 / NEMA Type 3, 3S, 4, 4X, 6, 6P, or 13 enclosure rating. Sealing rating (front panel only): NEMA Type 4 hose-down protection (UL certified) and IP65 (TRAC Global certified)
Electrical safetyEN 61010-1 UL61010-1, 3rd Edition, 2012 - 05
LVD (safety)-
EMCImmunity/emissions: CAN/CSA-C22.2 No. 61010-1, 3rd Edition, 2012 - 05, suitable for heavy industrial locations
EnclosureMaterial: polycarbonate 294. Front panel material: (blue) silicone rubber, 60shore
SolderTin/lead (60/40%)
Power and signal connectorsTerminals: plug-in terminal blocks with screw connectors. Note: Use only terminals supplied by Spirax Sarco; otherwise, safety and approvals may be compromised. Cable size: 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG). Stripping length: 5 - 6 mm high temperature
Level sensorShielding type: shielded
Feedback, steam, and water flowmeter cables/wiresCores: 3-core (LP20/PA20), 2 or 3 (4 - 20mA transmitters). Size: 1 – 1.5 mm² (18 - 16 AWG). Maximum length: 100 m (328 ft). Recommended types: Prysmian (Pirelli) FP200, Delta Crompton Firetuf OHLS
0/4 - 20 mA output cable/wireType: twisted pair. Shielding type: shielded. Cores: 1. Size: 0.23 - 1 mm² (24 - 18 AWG). Maximum length: 100 m (328 ft)
RS485 communication cable/wiringType: EIA RS485 twisted pair. Shielding type: shielded. Pairs: 2 or 3. Size: 0.23 mm² (24 AWG). Maximum length: 1200 m (4000 ft). Recommended types: Alpha 6413 or 6414. LAN Cat 5 or Cat 5E ScTP (shielded), FTP (foil), or STP Alpha 6413 or 6414 may be used, limited to 600 m
Input technical dataLevel voltage: minimum voltage 0Vdc or 1V (over-range selection), maximum voltage 6Vdc (absolute maximum =7Vdc), input impedance 28 kΩ, accuracy 5% FSD operating range, repeatability 2.5% FSD operating range, resolution 14-bit (approximately 0.15 mV), sampling rate 260 Hz. Minimum current 0 mA, maximum current 20 mA, input impedance 110 Ω, repeatability 2.5% FSD operating range, resolution 14-bit (approximately 1uA), sampling rate 260 Hz. Level ‘out of range’ alarm - voltage: minimum alarm level < 0.2 Vdc, minimum recovery level > 1 Vdc, maximum alarm level > 6.5 Vdc, maximum recovery level < 6 Vdc. Level ‘out of range’ alarm - current: minimum alarm level < 2.5 mA, minimum recovery level > 4 mA, maximum alarm level > 21 mA, maximum recovery level < 20 mA. 24 Vdc supply: maximum voltage 32 Vdc (no load, open circuit), maximum current 25 mA, ripple voltage 10 mV at full load. 4 - 20 mA: minimum current 0 mA, maximum current 22 mA, open-circuit loop voltage 19 Vdc (maximum), resolution 1% FSD, maximum output load 500 ohms, isolation 100 V, output rate 10 / second
OutputContacts: 2 × single-pole changeover relays (SPCO). Rated voltage (maximum): 250 Vac. Relay: resistive load 3 amp @ 250 Vac, inductive load 1 amp @ 250 Vac, AC motor load ¼ HP (2.9 amp) @ 250 Vac, 1 / 10 HP (3 amp) @ 120 Vac, pilot duty C300 (2.5 amp) - control circuit/coil. Electrical life (operations): 3 x 10⁵ or greater, depending on load. Mechanical life (operations): 30 x 10⁶
RS485Physical layer: RS485 4-wire full-duplex or 2-wire half-duplex. Protocol layer: Modbus RTU format. Isolation: 60 Vac/dc. Receiver unit load: 256 devices (maximum). Output rate: up to 10 frames/second
Infrared communicationsPhysical layer: IrDA. Baud rate: 38400. Range: 10 cm. Operating angle: 15 °. Eye safety information: Summary: EN 60825-12 : 2007, Safety of laser products - not exceeding Class 1 accessible emission limits (AEL)

Safety Information, Installation, and Maintenance

Warning: This document does not contain sufficient information for safe product installation. The product operates at hazardous voltages. Refer to the installation and maintenance instructions supplied with the product before installation.

Caution: Ensure that there is no condensation inside the product before installation and connection of the power supply. The product can be DIN rail, baseplate, or panel mounted and is supplied with an instrument bezel. It must be installed in a suitable industrial control panel or flameproof enclosure to provide protection against impact and environmental conditions. A minimum rating of IP54 (EN 60529) or Type 3, 3S, 4, 4X, 6, 6P, and 13 (UL50/NEMA 250) is required. Spirax Sarco supplies suitable plastic and metal enclosures.

  • Do not install outdoors without additional weather protection.

  • Do not attempt to open the product; it is sealed and contains no replaceable parts or internal switches.

  • Do not obstruct the infrared beam between products.

In the UK, follow IEE regulations (BS 7671). In other regions, follow the applicable regulations. All wiring materials and procedures must comply with the relevant EN and IEC standards.

No special servicing, preventive maintenance, or product inspection is required. Boiler water level controls and alarms must be tested and checked. Health and safety guidance BG01 and INDG436 provides general guidance.

Weight

550g