Description

Spirax Sarco LC3050 level controller is designed for high- and low-level alarms in conductive liquids and is defined in EN 12592-11 as a “specially designed water-level limiter.” It is suitable for steam or hot-water boilers with an operating limit of 32bar@239°C. The controller supports dual-voltage power supply, 230Vac or 115Vac, and is used with Spirax Sarco high- or low-level, self-monitoring high-accuracy level sensors. Two LEDs indicate normal and alarm conditions, and one test button (AL) is provided; other buttons are not used. The product supports panel, DIN-rail, or baseplate mounting. Every few seconds, the controller internally simulates a probe fault to perform an automatic cyclic test of the probe, probe cable, and controller. A test button enables comprehensive testing of the sensor, controller, and associated circuit. A remote test button can be provided if required.

Key Features

  • High-accuracy, high- or low-level self-monitoring

  • UL and TÜV certified

  • Dual voltage, 230/115Vac

  • LED status indication

  • Infrared communication

Certifications

LC3050 complies with EMC Directive 2004/108/EC and its requirements. The product meets all directive requirements for Class A environments, such as industrial locations, and complies with the following standards:

  • EN 61326-1:2006, electrical equipment for measurement, control, and laboratory use.

  • EMC Part 1 requirements: Class 1 requirements.

  • EN12953-9:2007 - Shell boilers, Part 9: Requirements for limiting devices of the boiler and accessories.

  • EN 12952-11:2007 - Water-tube boilers and auxiliary installations, Part 11: Requirements for limiting devices of the boiler and accessories.

  • Type-tested as a specially designed water-level limiting controller in accordance with Vd TÜV Water Level 100 (07:2006) for water-level control and limiting devices.

  • Complies with the Low Voltage Directive (2006/95/EC) and meets the following standard:

EN 61010-1:2001, safety requirements for electrical equipment for measurement, control, and laboratory use.

  • UL Listed (open)

Function / Inputs / Outputs

The controller normally activates an alarm relay to signal that the liquid level in a steam or hot-water boiler, tank, or vessel has moved outside the normal range. Spirax Sarco high-accuracy self-monitoring sensors can indicate internal faults and leakage. The controller compares the sensor resistance to earth through the water to the boiler or vessel shell. If a change in water level causes the resistance to exceed the set point, the timer changes the state of the internal relay after a preset delay. The signal is normally used to trigger an alarm and cut off power to the burner.

The product accepts inputs from LP30 low-level sensors and LP31 high-level sensors. At a normal water level, the green LED illuminates and the boiler panel indicates a normal water level. Every few seconds, the green LED briefly switches off to indicate that an automatic cyclic test is in progress. If a sensor fault is caused by an internal wiring fault or leakage, the compensation probe in the sensor issues an alarm signal. Parameters can be transmitted through RS485/MODBUS communication.

Additional Features

LC3050 can communicate with an adjacent controller through infrared communication. The LC3050 alarm status can be transmitted to a user-supplied RS485 device. The user device can include a graphical display. LC3050 is defined as a slave and requires no setup or adjustment.

Technical Specifications

ParameterDetails
Power supplySupply voltage: 220 / 240 Vac (198 V - 264 V), 110 / 120 Vac (99 V - 132 V)<br>Supply frequency: 50 - 60 Hz<br>Power consumption: 230 V / 30 mA or 115 V / 60 mA
EnvironmentIndoor use only<br>Maximum altitude: 2000m (6562ft)<br>Ambient temperature range: 0 - 55 °C<br>Maximum relative humidity: 80% at 31 °C, linearly decreasing to 50% at 40 °C<br>Overvoltage category: III<br>Pollution degree: 2 (as supplied), 3 (when installed in an enclosure)<br>Ingress protection: Minimum IP54 or UL50 / NEMA Type 3, 3S, 4, 4X, 6, 6P, or 13 (front panel only) IP65 (verified by TRAC Global)
Safety-related standardsElectrical safety: EN 61010-1, UL61010-1, CAN / CSA C22.2 No. 61010-1
EMCImmunity/emissions: Suitable for heavy industrial locations
EnclosureMaterial: Polycarbonate<br>Front panel material: Silicone rubber, 60shore
SolderTin/lead (60 / 40%)
Cable/wire and connector dataPower and signal connectors: Pluggable terminal blocks with screw connectors (use only terminals supplied by Spirax Sarco; otherwise, safety and approvals may be compromised)<br>Cable size: 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG)<br>Stripping length: 5 - 6 mm
Level sensor cable/wireType: High-temperature<br>Shielding type: Shielded<br>Number of cores: 4-core<br>Size: 1 – 1.5 mm² (18 - 16 AWG)<br>Maximum length: 50 m (164 ft)<br>Recommended types: Prysmian (Pirelli) FP200, Delta Crompton Firetuf OHLS
Input technical dataMinimum conductivity: 30 µS/cm or 30 ppm at 25 °C
Output technologyContacts: 2 x single-pole changeover relays (SPCO)<br>Relay voltage rating (maximum): 250 Vac<br>Resistive load: 3 amp @ 250 Vac<br>Inductive load: 1 amp @ 250 Vac<br>AC motor load: ¼ HP (2.9 amp) @ 250 Vac, 1 / 10 HP (3 amp) @ 120 Vac<br>Pilot duty rating: C300 (2.5 amp) - control circuit/coil<br>Electrical life (operations): 3 x 10 5 or greater, depending on load<br>Mechanical life (operations): 30 x 10 6
Infrared communicationPhysical layer: IrDA<br>Baud rate: 38 400<br>Range: 10 cm<br>Operating angle: 15 °<br>Eye safety information: Summary: EN 60825-12 : 2007 Safety of laser products - not exceeding Class 1 accessible emission limit (AEL)

Safety Information, Installation, and Maintenance

Warning: This document does not contain sufficient information for safe product installation. The product operates at hazardous voltages. Refer to the installation and maintenance guide supplied with the product before installing it.

Caution: Ensure that there is no condensation inside the product before installing and connecting the power supply. The product can be mounted on a DIN rail, baseplate, or panel. An instrument bezel is supplied. The product must be installed in a suitable industrial control panel or fireproof enclosure to provide protection against impact and environmental conditions. Minimum protection of IP54 (EN 60529) or Type 3, 3S, 4, 4X, 6, 6P, and 13 (UL50/NEMA 250) is required. Spirax Sarco supplies suitable plastic and metal enclosures.

  • Do not install outdoors without additional weather protection.

  • Do not attempt to open the product. It is sealed and contains no replaceable parts or internal switches.

  • Do not obstruct the infrared light between products.

In the UK, follow IEE regulations (BS 7671). In other regions, follow the applicable local regulations. All wiring materials and installation procedures must comply with the applicable EN and IEC standards. No special servicing, preventive maintenance, or product inspection is required. Boiler water-level controls and alarms must be tested and inspected. Health and safety guidance PM5 provides general guidance.

Weight

430g

How to Order

Example: 1 x Spirax Sarco LC3050 high-accuracy self-monitoring level controller.

WeChat ID copied