Description

Spirax Sarco S8 stainless steel steam separators DN65-DN350 remove liquids from steam, compressed air, and gas systems. For steam applications, an FT float trap and AV air vent must be installed. For compressed air/gas applications, a CA float drain trap must be installed.

Standards

This product complies with the European Pressure Equipment Directive 97/23/EC. Design and manufacture comply with EN 13445:2002 — “Unfired pressure vessels.”

Certificates

An EN 10204 3.1 material certificate is available. Other certificates can also be provided at an additional cost; please consult Spirax Sarco. If certificates are required, specify this when ordering.

Sizes and Pipe Connections

  • Sizes: DN65, DN80, DN100, DN125, DN150, DN200, DN250, DN300, DN350.

  • Flanged connections:

EN 1092 PN16 or PN40, with BSP threaded drain and vent connections.

  • ANSI B16.5 Class 150 or 300, with NPT threaded drain and vent connections.

  • JIS/KS 20K, with BSP threaded drain and vent connections.

  • Other connection options: threaded, socket-weld, and other connection types are also available; please consult Spirax Sarco.

Materials

All S8 components are made of austenitic stainless steel (304). For a carbon steel steam separator (S7), see T1-P138-03.

Pressure/Temperature Limits

SizeFlange standardDesign pressure bar gDesign temperature ℃Cold hydraulic test pressure bar g
DN65 to DN350PN161419821
ANSI 1502021330
JIS/KS 20K2321734.5
PN402522537.5
ANSI 3002522537.5
Note: If pressure and temperature exceed the operating conditions above, consult Spirax Sarco for a special order.

Weight

SizeDesign pressure (bar g)Weight (kg, approximate)
DN651447
2347
2547
DN801464
2364
2564
DN1001488
2388
2588
DN12514120
23120
25120
DN15014185
23185
25185
DN20014315
23315
25315
DN25014593
23593
25593
DN30014676
23676
25676
DN35014971
23971
25971

Safety Information, Installation, and Maintenance

See the installation and maintenance guide (IM-P023-55) supplied with the product.

Installation Instructions

To ensure effective condensate removal, install a suitable float trap and air vent. For compressed air/gas applications, install an equalizing line between the CA trap and the main pipeline or the top of the steam separator. Consult Spirax Sarco for detailed information.

Disposal

This product is recyclable and will not cause environmental harm when disposed of properly.

Spare Parts

S8 requires no maintenance and no spare parts are available.