Description
Spirax Sarco AEL7 series electric actuators are cost-effective electric actuators with linear output. They are suitable for Spirax Sarco Spira-trol two-way valves and QL three-way valves, as well as Hiter 85 series and 1000 series control valves. Actuators are normally supplied mounted on the control valve. When an actuator is supplied separately, ensure that the selected actuator provides sufficient thrust to close the two-way or three-way control valve at the expected differential pressure.
Available Models
This series is available with four power supply options: 230Vac, 115Vac, 24Vac and 24 Vdc. VMD control signals, (0)4 - 20mA control signals or (0)2 - 10Vdc control signals can be accepted. Auxiliary limit switches and anti-condensation heaters are also available. With the appropriate valve adapter and mounting flange, the actuators can be used with the following valves:
| Valve type | Size range | Compatible control valve series |
|---|---|---|
| Two-way valves | DN15 - DN300 | Spira-trol™ L, K and J series control valves, Hiter85 and 1000 series |
| Three-way valves | DN15 - DN300 | QL series control valves |
Warning
Installation of AEL7 series actuators requires connection to a power supply. Installers must have specialist knowledge of electrical circuits, systems and inherent hazards, as well as an understanding of linear actuator operation. Only qualified personnel may operate actuators under these conditions.
Standards and Certifications
This equipment is certified to comply with the following standards:
| Certification category | Standard |
|---|---|
| Electrical safety | 2014/35/EU (Low Voltage Directive) |
| Operational safety | EN 60204 - 1:2018 (Machinery Directive), EN14597 (AEL7T only; temperature control devices and temperature limiters for heating systems) |
| Operating requirements | EN15714 - 2 (Industrial valves — Electric actuators for industrial valves — Basic requirements), Class C modulating actuator compliant with DIN EN ISO 22153 |
| Installation requirements | EN 61000 - 6 - 4:2007/A1:2011 (Electromagnetic compatibility), EN 60529:92 + A1:00 + A2:13 (Degrees of protection provided by enclosures) |
| Material requirements | REACH and UK REACH |
Certification option: L and K series DN15 - 100 valves assembled with AEL7T spring-return actuators can be supplied with EN14597 certification for the complete valve and actuator assembly. This must be specified when ordering. EN14597 certification applies only to DN15 - 100 valves with T - 431 stainless steel seat options and standard trim. All other sizes, valve trims and seat options are outside the scope of this safety standard.
AEL7 Technical Specifications
| Actuator model | Thrust (KN) | Full-load speed (mm/s) @ 24 Vac – 240 Vac (50/60Hz) | Full-load speed mm/s @ 24 Vdc | Set stroke (mm) | Maximum stroke (mm) | Motor brake | Ambient temperature | Medium temperature | Enclosure rating | Housing material | Manual control device | Conduit entry | Electrical connection | Adapter | AEL7 actuator options |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Low | Medium | High | Low | Medium | High | ||||||||||
| AEL71 | 1.2 | 0.2 | 0.5 | 20 | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP54 | Thermoplastic, steel | Manual crank | ||||||
| AEL71T | 0.9 | 0.29 | 30 | 35 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP54 | Thermoplastic, steel | Manual crank | |||||
| AEL72 | 2.0 | 0.4 | 1.7 | 0.8 | 1.7 | 40 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP65 | Thermoplastic, steel | Manual crank | |||
| AEL72T | 2.1 | 0.29 | 35 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP54 | Thermoplastic, steel | Manual crank | ||||||
| AEL73 | 4.0 | 0.4 | 0.8 | 0.8 | 40 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP54 | Thermoplastic, steel | Manual crank | ||||
| AEL74 | 6.0 | 0.6 | 0.8 | 50 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP65 | Thermoplastic, steel | Manual crank | |||||
| AEL75 | 8.0 | 0.7 | 1.4 | 0.7 | 1.4 | 60 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP65 | Thermoplastic, steel | Manual crank | |||
| AEL76 | 12.0 | 0.4 | 0.4 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP65 | Thermoplastic, steel | Manual crank | ||||||
| AEL77 | 15.0 | 0.4 | 0.4 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP65 | Thermoplastic, steel | Manual crank | ||||||
| AEL78 | 20.0 | 0.8 | 1 | 70 | 100 | Vac versions only | -20 °C … +60 °C | -20 °C … +300 °C (425 °C under an extended bonnet 6) | IP65 | Thermoplastic, steel | Manual crank |
Notes: 1. 24 Vdc version unavailable. 2. Positioning plate required. 3. Actuators are supplied with this set stroke; actuator stroke can be adjusted to the maximum stroke. See IM - P713 - 01. 4. Standard supply; other options are available at additional cost. See the installation table for configuration requirements. 5. Factory installation only; cannot be retrofitted in the field. 6. The bonnet must not be insulated.
Materials
| Item | Description | Material | Surface finish |
|---|---|---|---|
| 1 | Cover | Polycarbonate (1 - 6 kN), carbon steel (8 kN +) | None, painted |
| 2 | Housing | Machined aluminum, cast aluminum | None, painted |
| 3 | Cover nut 1 | Polycarbonate (1 - 6 kN), carbon steel (8 kN +) | None, electroplated zinc |
| 4 | Handwheel 2 | Polycarbonate (8 kN +) | None |
| 5 | Manual/automatic selector lever | Carbon steel | Painted |
| 6 | Actuator stem | Carbon steel | None |
| 7 | Stroke indicator | Carbon steel | None |
| 8 | Anti-rotation plate and indicator | Carbon steel | None |
| 9 | Actuator pillar | Carbon steel | Electroplated zinc |
| 10 | Pillar nut | Carbon steel | None |
| 11 | Actuator adapter | Carbon steel | None |
| 12 | Protective cover (1.2 kN models only) | EPDM | None |
Notes: 1. For 1 - 6 kN actuators, an internal O-ring seal replaces the gasket. 2. 1 - 4 kN actuators use one manual crank.
Valve Adapter and Mounting Flange Selection
-
Spira - trol™ K & L
| Actuator | Thrust | DN15 - 50 | DN65 - 100 | DN125 - 300 |
|---|---|---|---|---|
| Flange | Threaded | Adapter | ||
| AEL71 | 1.2 kN | EL5970 | Integral | |
| AEL71T | 0.9 kN | M8 | AEL7XM8 1 | EL5971 |
| AEL72 | 2.0 kN | |||
| AEL72T | 2.1 kN | |||
| AEL73 | 4.0 kN | |||
| AEL74 | 6.0 kN | |||
| AEL75 | 8.0 kN | |||
| AEL76 | 12.0 kN | |||
| AEL77 | 15.0 kN | |||
| AEL78 | 20.0 kN |
Notes: 1. Included in the standard supply range for AEL71 through AEL75. 2. Adapter must be ordered separately.
-
Spira - trol™ J
| Actuator | Thrust | DN15 - 50 | DN65 - 100 | DN125 - 300 |
|---|---|---|---|---|
| Flange | Threaded | Adapter | ||
| AEL71 | 1.2 kN | EL5971J | M8 | AEL7XJ01 1 |
| AEL71T | 0.9 kN | EL5972J | M12 | AEL7XJ02< |